MULTIPOINT FFRoom Sealed Fan-Assisted Water Heater6 720 607 160 GB (06.04) ALPlease leave these instructions with the userUser Operating, Installation
10 6 720 607 1608. Siting the Flue TerminalSee Fig. 7.8.1 The flue must be installed as specified in BS5440:Part 1.8.2 The terminal must not cause an
116 720 607 1609. Air Supply9.1 The appliance does not require a separate vent forcombustion air.9.2 The appliance may be installed in an unventedcomp
12 6 720 607 160Fig. 85 Temperature sensor6 Water flow sensor7 Fuse1,25A8 Fuse 2A92 Gas valve117 Ignition electrode118 Sensing electrode119 Temperatur
136 720 607 160The installation must be carried out by a competent person.12.1 INITIAL PREPARATION12.1.1 Unpack the appliance and take care to remove
14 6 720 607 160Fig. 1212.2 FLUE RESTRICTIONThe Installation notes in these Instructions, particularly thoseregarding Maximum Flue Lengths and Configu
156 720 607 160Measure40mmTopViewWallRearFlueSideFlue10mmWallThicknessDrip Ring10mmFig. 1412.3.1 Standard Telescopic Flue Installation:Determine appro
16 6 720 607 16012.4 FITTING A VERTICAL FLUEPossible configurations of flue are as per Fig. 17.Vertical flue kits and flue extension components are de
176 720 607 16012.4.2 Extended Vertical InstallationVertical flue lengths may be extended to the limits as statedin Table 9 using standard 1m extensio
18 6 720 607 160Fig. 22Before commissioning the appliance, the gas installationmust be purged and tested for gas soundness in accordancewith BS 6891.1
196 720 607 16014. Inspection and ServicingWarningIsolate electrical supply before servicing the appliance.For reasons of safety and economy it is rec
2 6 720 607 160Natural GasMain Multipoint FFG.C. No 52-467-02User informationYour Main Multipoint FF is designed to meet all relevantstandards.Main pr
20 6 720 607 16014.5 Service adjustment14.5.1 Max and Min gas rate adjustmentDo NOT use magnetic tools to adjust the gas valve.Always adjust the MAXIM
216 720 607 16014.5.3 Temperature range selectionAppliance temperature range is set to 35°C - 60°C.Placing jumper JP7, temperature range changes to 38
22 6 720 607 16015. Replacement of partsWarning: Isolate electrical supply before servicing theappliance.Any servicing or parts replacement must be ca
236 720 607 160as per Section 15.5.1.15.6 Control UnitUnfasten the two screws securing the front panel of thecontrol unit and remove. Disconnect inlet
24 6 720 607 16016. Fault FindingNote: Installation, maintenance and repairs must be carried out only by a competent person.
256 720 607 16017. Short Parts ListItemBaxi Potterton NumberSpark Electrode 5111115Sensing Electrode 5111116Flow Sensor 5111117Control Unit 5111118Fus
18. Notes
GENERAL ENQUIRIES (GB)08706 060 780TECHNICAL (GB)08706 049 049SERVICE (GB)08706 096 096LITERATURE REQUEST (GB)08706 060 623TECHNICAL (IE)1850 560 570B
36 720 607 1601. User’s operating instructions ...42. General layout ...
4 6 720 607 1601. User’s Operating InstructionsSwitching on and off:On1. Turn the main switch to position I.Water temperature control:1. Turn the cont
56 720 607 1602. General LayoutFig. 3Appliance water flow diagram.Fig. 4Appliance components4 Electronic control box5 Heat sensor6 Water flow sensor10
6 6 720 607 1603. Technical DataThe appliance and flue components are packed in separate cartons.The appliance is for use with Natural Gas only.The In
76 720 607 1604. Dimensions and FixingsFig. 5
8 6 720 607 1605. General Information5.1 GENERAL INSTALLATIONIf the appliance is to be fitted into a compartment, thecompartment must conform to the r
96 720 607 1607. Siting the Appliance7.1 The appliance is NOT suitable for external installation.7.2 The appliance is NOT suitable for SEDUCTapplicati